# UPS-MIB
# Statistics about your UPS using the UPS-MIB from the RFC1628.
#
+ # Battery branch
+ <Data "upsmib_timeleft_battery">
+ Type "timeleft"
+ Table false
+ Instance "battery"
+ Values ".1.3.6.1.2.1.33.1.2.3.0"
+ </Data>
<Data "upsmib_charge_battery">
Type "percent"
Table false
Table false
Instance "battery"
Values ".1.3.6.1.2.1.33.1.2.5.0"
+ Scale 0.1
+ </Data>
+ <Data "upsmib_current_battery">
+ Type "current"
+ Table false
+ Instance "battery"
+ Values ".1.3.6.1.2.1.33.1.2.6.0"
+ Scale 0.1
+ </Data>
+ <Data "upsmib_temperature_battery">
+ Type "temperature"
+ Table false
+ Instance "battery"
+ Values ".1.3.6.1.2.1.33.1.2.7.0"
+ </Data>
+ # Input branch
+ <Data "upsmib_frequency_input">
+ Type "frequency"
+ Table true
+ InstancePrefix "input"
+ Values ".1.3.6.1.2.1.33.1.3.3.1.2"
+ Scale 0.1
</Data>
<Data "upsmib_voltage_input">
Type "voltage"
InstancePrefix "input"
Values ".1.3.6.1.2.1.33.1.3.3.1.3"
</Data>
+ <Data "upsmib_current_input">
+ Type "current"
+ Table true
+ InstancePrefix "input"
+ Values ".1.3.6.1.2.1.33.1.3.3.1.4"
+ Scale 0.1
+ </Data>
+ <Data "upsmib_power_input">
+ Type "power"
+ Table true
+ InstancePrefix "input"
+ Values ".1.3.6.1.2.1.33.1.3.3.1.5"
+ </Data>
+ # Output branch
+ <Data "upsmib_frequency_output">
+ Type "frequency"
+ Table false
+ Instance "output"
+ Values ".1.3.6.1.2.1.33.1.4.2.0"
+ Scale 0.1
+ </Data>
<Data "upsmib_voltage_output">
Type "voltage"
Table true
InstancePrefix "output"
Values ".1.3.6.1.2.1.33.1.4.4.1.2"
</Data>
+ <Data "upsmib_current_output">
+ Type "current"
+ Table true
+ InstancePrefix "output"
+ Values ".1.3.6.1.2.1.33.1.4.4.1.3"
+ Scale 0.1
+ </Data>
+ <Data "upsmib_power_output">
+ Type "power"
+ Table true
+ InstancePrefix "output"
+ Values ".1.3.6.1.2.1.33.1.4.4.1.4"
+ </Data>
+ <Data "upsmib_load_output">
+ Type "percent"
+ Table true
+ InstancePrefix "load-output"
+ Values ".1.3.6.1.2.1.33.1.4.4.1.5"
+ </Data>
+ # Bypass branch
+ <Data "upsmib_frequency_bypass">
+ Type "frequency"
+ Table false
+ Instance "output"
+ Values ".1.3.6.1.2.1.33.1.5.1.0"
+ Scale 0.1
+ </Data>
<Data "upsmib_voltage_bypass">
Type "voltage"
Table true
InstancePrefix "bypass"
Values ".1.3.6.1.2.1.33.1.5.3.1.2"
</Data>
- <Data "upsmib_current_battery">
+ <Data "upsmib_current_bypass">
Type "current"
+ Table true
+ InstancePrefix "bypass"
+ Values ".1.3.6.1.2.1.33.1.5.3.1.3"
+ Scale 0.1
+ </Data>
+ <Data "upsmib_power_bypass">
+ Type "power"
+ Table true
+ InstancePrefix "bypass"
+ Values ".1.3.6.1.2.1.33.1.5.3.1.4"
+ </Data>
+ # Special definitions for broken UPSes
+ <Data "upsmib_voltage_battery_unscaled">
+ Type "voltage"
Table false
Instance "battery"
- Values ".1.3.6.1.2.1.33.1.2.6.0"
+ Values ".1.3.6.1.2.1.33.1.2.5.0"
</Data>
- <Data "upsmib_current_input">
+ <Data "upsmib_current_input_unscaled">
Type "current"
Table true
InstancePrefix "input"
Values ".1.3.6.1.2.1.33.1.3.3.1.4"
</Data>
- <Data "upsmib_current_output">
+ <Data "upsmib_current_output_unscaled">
Type "current"
Table true
InstancePrefix "output"
Values ".1.3.6.1.2.1.33.1.4.4.1.3"
</Data>
- <Data "upsmib_current_bypass">
- Type "current"
- Table true
- InstancePrefix "bypass"
- Values ".1.3.6.1.2.1.33.1.5.3.1.3"
- </Data>
- <Data "upsmib_temperature_battery">
- Type "temperature"
- Table false
- Instance "battery"
- Values ".1.3.6.1.2.1.33.1.2.7.0"
- </Data>
#
# Riello UPS
</Data>
#
+ # PowerPlus UPS, manufactured by Gamatronic, <http://www.gamatronic.com/>,
+ # distributed in Germany by AdPoS, <http://adpos-usv.de/>
+ #
+ # Global inputs
+ <Data "powerplus_voltage_input">
+ Type "voltage"
+ Table true
+ InstancePrefix "input"
+ Values ".1.3.6.1.4.1.6050.5.4.1.1.2"
+ </Data>
+ <Data "powerplus_current_input">
+ Type "current"
+ Table true
+ InstancePrefix "input"
+ Values ".1.3.6.1.4.1.6050.5.4.1.1.3"
+ </Data>
+ <Data "powerplus_power_apparent_input">
+ Type "power"
+ Table true
+ InstancePrefix "apparent-input"
+ Values ".1.3.6.1.4.1.6050.5.4.1.1.4"
+ Scale 100.0
+ </Data>
+ <Data "powerplus_power_active_input">
+ Type "power"
+ Table true
+ InstancePrefix "active-input"
+ Values ".1.3.6.1.4.1.6050.5.4.1.1.5"
+ Scale 100.0
+ </Data>
+ <Data "powerplus_performance_factor_input">
+ Type "percent"
+ Table true
+ InstancePrefix "performance_factor-input"
+ Values ".1.3.6.1.4.1.6050.5.4.1.1.6"
+ </Data>
+ # Global outputs
+ <Data "powerplus_voltage_output">
+ Type "voltage"
+ Table true
+ InstancePrefix "output"
+ Values ".1.3.6.1.4.1.6050.5.5.1.1.2"
+ </Data>
+ <Data "powerplus_current_output">
+ Type "current"
+ Table true
+ InstancePrefix "output"
+ Values ".1.3.6.1.4.1.6050.5.5.1.1.3"
+ </Data>
+ <Data "powerplus_power_apparent_output">
+ Type "power"
+ Table true
+ InstancePrefix "apparent-output"
+ Values ".1.3.6.1.4.1.6050.5.5.1.1.4"
+ Scale 100.0
+ </Data>
+ <Data "powerplus_power_active_output">
+ Type "power"
+ Table true
+ InstancePrefix "active-output"
+ Values ".1.3.6.1.4.1.6050.5.5.1.1.5"
+ Scale 100.0
+ </Data>
+ <Data "powerplus_load_level_output">
+ Type "percent"
+ Table true
+ InstancePrefix "load_level-output"
+ Values ".1.3.6.1.4.1.6050.5.5.1.1.6"
+ </Data>
+ <Data "powerplus_active_load_level_output">
+ Type "percent"
+ Table true
+ InstancePrefix "active_load_level-output"
+ Values ".1.3.6.1.4.1.6050.5.5.1.1.7"
+ </Data>
+ <Data "powerplus_performance_factor_output">
+ Type "percent"
+ Table true
+ InstancePrefix "performance_factor-output"
+ Values ".1.3.6.1.4.1.6050.5.5.1.1.8"
+ </Data>
+ # Global DC
+ <Data "powerplus_global_dc_positive">
+ Type "voltage"
+ Table false
+ Instance "dc_positive-global"
+ Values ".1.3.6.1.4.1.6050.5.6.1.0"
+ </Data>
+ <Data "powerplus_global_dc_negative">
+ Type "voltage"
+ Table false
+ Instance "dc_negative-global"
+ Values ".1.3.6.1.4.1.6050.5.6.2.0"
+ </Data>
+ <Data "powerplus_global_dc_total">
+ Type "voltage"
+ Table false
+ Instance "dc_total-global"
+ Values ".1.3.6.1.4.1.6050.5.6.3.0"
+ </Data>
+
+ #
# NetApp
# Some simple statistics of storage systems by NetApp.
#